Field calculation tool

Load Bank Calculator

Calculate common generator load steps, or convert AC amps and kW with an explicit power-factor basis.

Generator inputs Resistive load · PF 1.0
System phase

Voltage is line-to-line for three-phase calculations. Current shown is expected line current.

Calculated load steps 500 kW · 480 V · 3Ø
25%
125.0kW
150.4A
50%
250.0kW
300.7A
75%
375.0kW
451.1A
100%
500.0kW
601.4A
Calculation basis

Three-phase current = kW × 1,000 ÷ (√3 × voltage × power factor).

Calculation basis

This tool calculates expected current for a unity-power-factor resistive load bank. A generator’s nameplate current may be based on its kVA rating at a lower power factor, so full rated kW on a resistive bank may not equal nameplate full-load amps.

Use these values for planning—not as conductor sizing, connection approval, or proof of a required test procedure.